Support For Installers
We Are Together
LIVOLTEK places a high value on relationships with our partners around the world. If you encounter any problems during the distribution or installation of our products, please feel free to contact us and we will arrange for our local technical teams to assist you as soon as possible.
Here you can find some useful tips before installing our products, as well as the most common problems you may encounter during troubleshooting.
Tips
After the battery is installed for the first time, you are advised to charge the battery forcibly (for calibration Battery).
1)Tighten the cable gland
2)Idle interfaces are sealed
3)The cable entry cover is closed
4)Conduit sealing treatment
5)Confirm and lock the waterproof cap
There are 4 types of EPS modes, they are:
0 – Disable
1 – EPS without bypass:only in the case of power failure, EPS port will have voltage output (basically no standby power consumption)
2 – EPS with bypass:When there is power grid, EPS port will also have voltage output, and when power failure, EPS port voltage will need about 2s for output switch (low power standby power consumption).
3 – UPS with bypass:EPS port also has voltage output when there is power grid, and UPS mode output when power failure, EPS port voltage needs <20ms time for switching (high power standby power consumption)
1) Do a good job of line marking to reduce the probability of
errors
2) Before connecting to the inverter, use a multimeter to measure the input voltage of the component on the positive and negative sides to ensure that the polarity is correct and does not exceed the maximum input voltage
3) Use special crimping tools for photovoltaic terminals
4) If conditions permit, you can use an infrared thermal imager or a spot temperature gun to confirm the connection point temperature after grid-connected power generation.
Vertical installation/ Do not allow lying down/ Leaning back and inversion
FAQ
1)Make sure to use terminal blocks for lock wire
2)Make sure the terminals are locked
3)Do not lock the screw to the cable insulation
1) When connecting photovoltaic modules to the inverter, the Amphenol H4 photovoltaic special connector provided with the inverter should be used. Compatible models may not guarantee long-term effective contact of metal terminals.
2) When crimping the positive metal terminal, do not also crimp the limit stop bar, otherwise the metal terminal will not be stuck, resulting in “heading”
3)Strictly prevent the reverse polarity of the DC input. It is forbidden to connect the single group in series in the same MPPT. Make sure that the terminal is correct before inserting the terminal into the inverter (it is recommended to use a multimeter to measure)
1)Pay attention to the correct connection of the neutral wire polarity
2)It is forbidden to connect the load to the output terminal of the inverter without passing through the circuit breaker;
3)Each inverter needs to be equipped with an independent circuit breaker to ensure safe disconnection from the grid
4)When using multiple single-strand cables for AC output, use fireproof mud to seal the gap between the sealing ring and the cable after wiring is completed.
5)When a large number of single-phase output inverters are connected to the same low-voltage transformer in the three-phase power grid, attention should be paid to the reasonable distribution of the inverters among the three phases, and the load balance of the three phases should be maintained as much as possible to avoid the failure of a certain phase due to insufficient consumption. The phase voltage rises and damages the electrical equipment;
Troubleshooting
1. On-grid Inverter
Product Name | Alarm Definition | Processing Strategies |
A00-Grid AC over voltage | The grid voltage exceeds the allowable range | 1. If the alarm occurs occasionally, it means the grid abnormal, the inverter can automatically recover to normal operating status after the grid return normal. 2. If the alarm occurs repeatedly and it can automatically recover, need to contact local electric power department to get permission to modify the inverter grid protection parameters with APP. 3. If the alarm occurs repeatedly for a long time, please confirm 1) If the output breaker is closed? 2)If the output terminal is ok? 3)If grid is power off? 4)If the output cable follow the User Manual guidance? |
A01-Grid AC under voltage | ||
A02-Grid AC absent | The grid voltage is 0 volt | |
A03-Grid AC over frequency | The grid frequency exceeds the allowable range | |
A04-Grid AC under frequency | ||
B00-PV DC over voltage | PV module input voltage is higher than the allowable range | Please measure the PV input voltage with multimeter, and compare it with the “Max input voltage” written the inverter lable. If PV input voltage is larger than “Max input voltage”, then reduce the PV module quantity. |
B01-PV insulation abnormal | The insulation resistance against the ground is lower than the allowable range | 1. If the alarm occurs occasionally, it may be caused by external circuit, the inverter can automatically recover to normal operating status after the fault is cleared. 2. If the alarm occurs repeatedly or lasts a long time, please follow below steps: 1) Check if the output cable is stable. 2) Plug the PV strings one by one to find the abnormal PV strings. Please check if the insulation resistance against the ground of PV strings is too low, or the cable is broken, or cable connection incorrectly. |
B02-Leakage current abnormal | The residual current is high. | 1. If the alarm occurs occasionally, it may be caused by external circuit, the inverter can automatically recover to normal operating status after the fault is cleared. 2. If the alarm occurs repeatedly or lasts a long time, please follow below steps: 1) Check if the output cable is stable. 2) Plug the PV strings one by one to find the abnormal PV strings. Please check if the insulation resistance against the ground of PV strings is too low, or the cable is broken, or cable connection incorrectly. |
B03-PV string abnormal | PV strings have been shielded for a long time or PV strings is abnormal | 1. Check whether the PV string is shielded. 2. If the PV string is clean and not shielded, check if the PV modules are aging or deteriorated, or if cable/terminal is abnormal. |
B04-PV DC under voltage | PV modules input voltage is under default protection value. | 1. If alarm occur during sunlight weak(At morning or dawn, raining or ), it’s normal and no action is needed. 2. If not, please check if there is PV module connection short circuit. |
A06-Grid voltage unbalanced | The grid voltage unbalanced exceeds the allowable range | 1. If the alarm occurs occasionally, it means the grid abnormal, the inverter can automatically recover to normal operating status after the grid return normal. 2. If the alarm occurs repeatedly and it can automatically recover, need to contact local electric power department to get permission to modify the inverter grid protection parameters with APP. 3. If the alarm occurs repeatedly for a long time, please confirm 1) If the output breaker is closed? 2)If the output terminal is ok? 3)If grid is power off? 4)If the output cable follow the User Manual guidance? |
C02-Output DC over current | Grid DC component current is higher than than the allowable range | 1. If the alarm occurs occasionally, it’s caused by grid voltage abnormal temporarily, the inverter can automatically recover to normal operating status, no action is needed. 2. If the alarm occurs repeatedly or lasts a long time, please contact customer service center. |
C03-Inverter relay abnormal | Internal relay abnormal | 1. If the alarm occurs occasionally, it’s caused by grid voltage abnormal temporarily, the inverter can automatically recover to normal operating status, no action is needed. 2. If the alarm occurs repeatedly or lasts a long time, please check if output neutral line and fire line reverse connection. If not, please contact customer service center. |
C05-Inverter over temperature | Internal temperature is higher than than the allowable range | 1. If the alarm occurs occasionally, the inverter can automatically recover to normal operating status, no action is needed. 2. If the alarm occurs repeatedly or lasts a long time, please check if the installation site is direct sunlight, ventilation is good, the ambient temperature is too high. If not, please contact cusomer service center. |
C06-Leakage current HCT abnormal | Residual current device test is failure | 1. If the alarm occurs occasionally, it may be caused by external circuit abnormal, the inverter can automatically recover to normal operating status after fault is cleared. 2. If the alarm occurs repeatedly or lasts a long time, please check if the insulation resistance against the ground of PV strings is too low, or the cable is broken, or cable connection incorrectly. |
B07-PV string reverse | The polar of PV strings is reversed. | Check whether the cables of PV strings are correctly connected. If they are connected reversely, reconnect the cables. |
C08-Fan lock | Fan abnormal | 1. If the alarm occurs occasionally, please restart inverter. 2. If the alarm occurs repeatedly or lasts a long time, please check if fan is blocked. If not, please contact customer service center. |
Energy Storage System
1.Common Customer Complaints-Installation Stage
Earth fault: F2: 00000001
S/N | Probable Cause | Recommended Measure |
1 | The inverter ground wire is not connected properly | 1.Check the inverter ground wire connection. 2.Check the voltage between N&E, it should be under 30V; If it is over 30V,check the connection of the home ground wire |
2 | The voltage between N&E is too high | |
3 | Inverter damaged | Replace inverter |
Meter Communication Failure: F3: 00000400
S/N | Probable Cause | Recommended Measure |
1 | The meter cable is not connected or the connected communication port is wrong | Check the meter connection wire harness and ports |
2 | Communication matching resistance is incorrect | Add matching resistance to the communication terminal of the meter |
3 | Inverter meter type setting is incorrect | Check the meter type parameter settings |
4 | The line sequence of the RJ45 head is incorrect or the line sequence of the communication port of the meter is incorrect. | Check the color and line sequence of the meter communication line according to the user manual |
5 | Bad meter communication harness | Replace the communication harness, UTP is recommended |
6 | Meter damaged | Replace meter |
7 | The meter communication port of the inverter is damaged | Replace meter |
BMS communication failure: F3: 00004000
S/N | Probable Cause | Recommended Measure |
1 | The BMS communication cable is not connected or the interface is incorrectly inserted | Check BMS wiring harness and connection ports |
2 | Inverter battery type parameter is incorrect | Check inverter parameters |
3 | Bad BMS communication harness | Replace the BMS communication harness, UTP is recommended |
4 | Bad battery BMS communication port | Replace battery |
5 | Bad inverter BMS communication port | Replace inverter |
2.Common Customer Complaints—Utilization Stage
When switching between on-grid and off-grid, the switching time of EPS ports is too long, which cause power failure of some loads.
S/N | Probable Cause | Recommended Measure |
1 | Inverter EPS mode setting is incorrect | Check the EPS mode setting. Setting 1 switching time is 2-3S, but the standby power consumption is the lowest, setting 2 switching time is about 1S, with bypass function, standby power consumption is low, setting 3 switching time 20ms, UPS function, standby power consumption average 50- 60W |
2 | When the grid is powered off, it is just in the inverter grid connection stage | UPS switching is not supported at this stage |
3 | There are too many rectified loads and inductive loads in the home, which will cause prolonged on-grid switching | When there are too many rectifying loads and inductive loads, the switching time can last for 30ms, and some loads will lose power, especially some lamps. |
4 | The EPS port is connected to an electrical appliance with an impulse starting current load, and exceeds the inverter load capacity | EPS ports cannot be connected to loads with high impulse current, such as water pumps |
PV does not generate power or generates little power
S/N | Probable Cause | Recommended Measure |
1 | Weather reason | Check historical data to see if it is weather reason |
2 | Set 0 feed in, to meet no feed in logic | Check settings |
3 | The system insulation resistance value is detected, but the inverter is in the standby state of connection | Check whether the inverter connection is stopped at 1, and check whether the system insulation resistance value is less than 30K |
4 | Inverter MPPT working mode parameter setting is incorrect | Check the MPPT working mode, it should set to 0 |
5 | The system working state is wrong or the bus voltage state is wrong | Confirm whether the system is in PV working state 5 or 6, and check whether the bus voltage is normal, 400V, 450V, 440V. If the status is wrong, try to restart the inverter |
Battery does not discharge
S/N | Probable Cause | Recommended Measure |
1 | The current battery SOC has reached or is lower than the preset discharge cut-off SOC value | Check the parameters |
2 | The battery is not allowed to discharge, for example, the BMS allows the discharge current to be 0 | Check BMS information, confirm battery working status |
3 | Inverter is set to backup mode or set to forced charging state | Check the inverter working mode setting and ES control status, 1 is self-use, 3 is forced charging, 5 is forced discharging |
4 | The battery voltage is under 50V | Check if the battery voltage is under 50V |
5 | The system working state is wrong or the bus voltage state is wrong | Confirm whether the system is in the battery working state 3 or 6, and check whether the bus voltage is normal, 400V, 450V, 440V. If the status is wrong, check whether the battery port of the inverter has voltage or try to restart the inverter |
6 | Inverter battery discharge circuit damaged | Replace inverter |
The battery does not charge
S/N | Probable Cause | Recommended Measure |
1 | The inverter set forced discharge | Confirm the status of ES control, 1 is for self-use, 3 is forced charging, 5 is forced discharging |
2 | The battery is not allowed to charge, the battery BMS allows the charging current to be 0 | Check BMS information to confirm battery working status |
3 | When charging stopped, the battery voltage is over 53.5V and does not meet the conditions for recharging | Check the battery history charging status, check the battery voltage curve |
4 | In spontaneous self-use mode, the load is larger than the PV power | Check the working status of the system to confirm whether it conforms to the working logic |
5 | The system working state is wrong or the bus voltage state is wrong | Confirm whether the system is in the battery working state 3 or 6, and check whether the bus voltage is normal, 400V, 450V, 440V. If the status is wrong, check whether the battery port of the inverter has voltage or try to restart the inverter |
6 | The inverter charging circuit is damaged | Replace Inverter |
Bus overvoltage fault :F1: 80000400
S/N | Probable Cause | Recommended Measure |
1 | Panel open circuit voltage is too high | Check and confirm the configuration of the panel, note the effect of temperature on the open circuit voltage of the panel |
2 | In off-grid mode, some loads with short-term impulse current will trigger | Some loads are not recommended to be connected to the EPS port, such as water pumps. If they must be connected, a soft starter needs to be added. |
3 | In the case of weak grid, the inverter control loop oscillates | Need to adjust software PI parameters |
4 | When in multiple machines parallel mode, the inverter is disturbed | Try to add an inductor at the grid end |
5 | Inverter damaged | Replace inverter |
Overcurrent fault F1: 18004800
S/N | Probable Cause | Recommended Measure |
1 | Some special loads will cause the inverter to report overcurrent, such as water pumps, washing machines, etc. | Try to add inductance at the grid end, soft start and other measures |
2 | When in multiple machines parallel mode, the inverter is disturbed and causes vibration | Try to add an inductor at the grid end |
3 | Inverter hardware damage | Replace inverter |
Grid-connected relay failure: F2: 00000010
S/N | Probable Cause | Recommended Measure |
1 | The inverter is disturbed by the grid | Try to restart the inverter, some old hardware version inverters can try to add an inductor on the grid side to solve the problem |
2 | There is a problem with the relay control circuit | |
3 | Grid end cement resistance failure | The cement resistance can be skipped by setting the parameter. Reserved 1 is set to 1 to not use the cement resistance, and set to 0 to use the cement resistance. |
Contact Form
Dear users, if you encounter any problems during the use or installation of Livoltek products, you are welcome to fill in the contact form below.
Our after-sales engineers will help you to solve the problem the first time.
Pakistan
ADD|Plot Number 13B & 14B , 109/M, Quaid e Azam Industrial Estate, Lahore, 54000
TEL/WhatsApp(Marketing) |0311 3698461
EMAIL(Sales) |sales.pk@livoltek.com
Headquarter
ADD|1418-35 Moganshan Road, Hangzhou, 310011, China
TEL/WhatsApp/WeChat(Sale)|+86 157 1576 8455
EMAIL(Sales)|info@livoltek.com
TEL/WhatsApp/WeChat(Service)|+86 151 5718 2502
EMAIL(Service)|service@livoltek.com
Netherlands
ADD|Westeind 8A, 5245 NL, Rosmalen, Netherlands
TEL/WhatsApp/WeChat(Sale)|+86 157 1576 8455
EMAIL(Sales)|sales.eu@livoltek.com
TEL/WhatsApp/WeChat(Service)|+86 151 5718 2502
EMAIL(Service)|service.eu@livoltek.com
Pakistan
ADD|Office#5,7th Floor Shaheen, Complex, Egerton Road, Lahore
TEL/WhatsApp/WeChat(Sales) |+86 157 1576 8455
EMAIL(Sales) |sales.pk@livoltek.com
TEL/WhatsApp/WeChat(Service) |+86 157 1576 8455
EMAIL(Service) |service.pk@livoltek.com
Brazil
Eletraenergy.
ADD|Rodovia BR 116, km 16, 7698
Pedras, Eusébio, Ceará, 61760-000, Brazil
TEL/WhatsApp/WeChat(Sales) |+55(085)98115-1834
EMAIL(Sales) |sales.br@livoltek.com
TEL(Service) |+55 11 93338-1338
EMAIL(Service) |suportebr@livoltek.com
South Africa
Hexing Electrical SA (Pty) Ltd.
ADD|82 Roan Crescent, Corporate Park North, Midrand, Johannesburg, South Africa
TEL/WhatsApp/WeChat(Sales)|+86 157 1576 8455
EMAIL(Sales)|sales.sa@livoltek.com
TEL(Service)|+27676848139
EMAIL(Service)|saservice@livoltek.com
Colombia
ADD|Cl. 99#10-08 Piso 7Bogotá, Colombia
TEL/WhatsApp/WeChat(Sales)|+57 311 8997451
EMAIL(Sales)|info@livoltek.com
TEL(Service)|+57 311 8997451
EMAIL(Service)|service@livoltek.com
Italy
LIVOLTEK ITALIA srl – via Ceradini 12 – 20129 Milano
TEL/WhatsApp/WeChat(Sale)|+86 157 1576 8455
EMAIL(Sales)|info@livoltek.com
TEL/WhatsApp/WeChat(Service)|+86 151 5718 2502
EMAIL(Service)|service@livoltek.com
U.K.
55 Holloway Head, Birmingham B1 1HP, UK
TEL/WhatsApp/WeChat(Sales)|+44 7597 587947
EMAIL(Sales)|info@livoltek.com
TEL(Service)tel:|+ 44 7597 587947
EMAIL(Service)|service@livoltek.com